Advanced Refrigeration Podcast

← Advanced Refrigeration Podcast21 Sept · 55 min

CO2 Condensing Units Whats My Interstage Pressure Supposed To Be ?? Want Some POP Episode 538 Audio

CO2 Condensing Units Whats My Interstage Pressure Supposed To Be ?? Want Some POP Episode 538 Audio21 Sept55 min

<p>CO₂ Single Condensing Units: Relief Valves, pRack Pain, and Dorin Two‑Stage DiagnosticsBrett Wetzel and Kevin Compass open the Advanced Refrigeration Podcast joking about “pop” in the Midwest before diving into CO₂ single condensing units as Brett teaches in Minnesota and discusses an SCM Frigo unit. They compare common controllers (Carel pRack/mini PAC, Danfoss, and Copeland possibilities), complain about limited tech-friendly navigation and lack of onboard trending, and discuss pulling data via Modbus/BACnet and supervisory options like Boss Mini. Brett reviews relief valve piping after seeing popped reliefs, critiques tight packaging and reliability, and notes issues like overcharging and mismatched evaporator/valve capacity that can empty a sight glass. They walk through SCM Frigo medium-temp piping, internal heat exchange, Carel E2V-C valves, BGV function, and oil system designs, then cover a Dorin two-stage low-temp unit with floating flash tank pressure and shared plenum cooling. Brett demonstrates using Dorin software to estimate expected interstage/flash tank pressure, amperage, and temperatures to diagnose performance without relying on pump-down tests, and points to the web-based version of the tool.</p>